Sets/returns the comparator value used for a negative direction soft-limit. 


Applies to: CMD-4CR, CMD-4EX-SA, Firmware V 2.01+


ASCII                SFLN[axis]        

Syntax:                        

Read:

SFLN[axis]                

Where:        [axis] is set to X, Y, Z, U


Write:

SFLN[axis]=[pos]                 

Where:        [axis] is set to X, Y, Z, U

[pos]      specifies target of negative soft-limit (28-bit value)

Reply: 

Command is accepted and executed

Read:         

Returns the comparator value of the [axis] negative direction soft-limit (28-bit value)


Write:           

OK


Command cannot be processed

       An error message is returned. See Error Codes

Example: 

Read:        

SFLNY                * Returns the comparator value of the Y axis negative direction soft-limit


Write:        

SFLNX=-6000 * Sets X axis negative direction soft-limit to -6000

Notes:

  • Before enabling soft-limits, check that softLimitPositive SFLP[axis] and softLimitNegative SFLN[axis] are different and that the positive value is greater than the negative value.  If not, an error is returned. 
  • Soft-limits act similarly to limit switches.  While the controller will command a stop when a soft-limit is encountered, it is possible to overrun the soft limit.  The amount the system can overrun the limit depends on the speed the motor is moving at when the soft-limit is encountered, and the mode selected for stopping the motor (SFLSD[axis]).  As such, a safety buffer should be included in any soft-limit settings. 

See also:

Limits/Safety Setup

SFL, SFLP, SFLSD, SFLSO

Commander Manual

2.1.3.1.1.4 Soft-Limits