CMD Homing Mode 4
Homing Mode 4
For homing mode 4, the motor decelerates upon reaching the home limit switch and reverses direction upon reaching the lower speed point. Home is set when the Z-index pulse is encountered.
Homing Mode |
Home Limit |
End Limits |
Z-index |
Slow Down |
Approaches Home at |
Direction to Trigger Zero |
Ending Point |
|
High Speed |
Low Speed |
|||||||
Mode 4 |
● |
|
● |
○ |
|
L |
Reverse Dir |
Zero |
Operation 1:
- Homing operation is started, accelerate from LSPD to HSPD.
- Begin deceleration after home limit is encountered.
- Reverse direction at LSPD after deceleration complete.
- Continue moving at LSPD until specified number of Z-Index pulses are counted (ZCNT).
- Operation stops and is completed; zero position is set.
- ERC pulse is sent.
Operation 2:
- Homing is started while home input is activated.
- acceleration from LSPD to HSPD.
- End limit is encountered, immediate stop.
Operation 3:
- Homing is started moving away from the home input switch.
- acceleration from LSPD to HSPD.
- End limit is encountered, immediate stop.
More information on the homing modes can be found in Section 9-5-1 of the PCL6045BL users manual.